Schneider Electric (APC) Make 160 KVA 3:3 Phase Industrial Easy On Line UPS | apcups.co.in

Contact Us

Support APC UPS System Schneider Electric (APC) Make 160 KVA 3:3 Phase Industrial Easy On Line UPS

Schneider Electric (APC) Make 160 KVA 3:3 Phase Industrial Easy On Line UPS

UPS System Industrial UPS

1103300

Easy UPS 3M 160kVA 400V 3:3 UPS for external batteries, Start-up 5x8 Easy-to-install, easy-to-connect, easy-to-use, and easy-to-service 160 kVA 3 phase UPS with advanced product features, robust electrical specifications and compact design making your business continuity easy. Ideal for small and medium data centers and other business critical applications, this UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management. It is supplied without batteries, so you can easily customize your battery solution. Includes 5x8 start-up service. Includes: Dust filter, Installation guide, Start-up service

Model E3MUPS160KHS

Reset default

Specification

Output Specification
Output Capacity (KVA )
160 Kva
Output Capacity (KW )
160 Kw
Output Power Factor
1 Power Factor
Output Phase
3 Phase
Other Output Phase
Or Phase
Output Voltage
400 Volt
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
>0.99 %
Output Voltage Distortion
<3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
3:1
Output Voltage THD
< 3% linear load and <5% non-linear load
Transfer Time
<0 Ms
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
UPS Parallel Upto
Optional
Input Specification
Input Voltage
400 Volt
Other Input Voltage
380 - 415 Volt
Input Phase
3 Phase
Other Input Phase
- Phase
Input frequency
50 Or 60 Hz
Input frequency Range
40 - 70 Hz
Input Voltage Range (Output Derated)
150 - 342 Volt
Input voltage range for main operations
342 - 477 Volt
Input Power Factor
>0.99 Power Factor
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Protection
Fuse
Input Voltage THD
<3 %
Input Short Circuit Current (Maximum)
10 kAmps.
Input Current (Maximum)
262 Amp.
Batteries & Runtime
Battery Position Option
External
Battery Circuit Breaker
Optional
Approved Battery Capacity (AH)
150 - 200 Amp.
Battery DC Bus
432 - 600 Vdc
Battery Type Compatibility
Sealed Maintenance Free (SMF) / Valve Regulated Lead Acid (VRLA) type, Flooded / tubular / vented type
Communication & Management
Control panel
Touch Screen LCD User Interface
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
E3M_ColdStart, E3M_parallel, E3S_TempSensor
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
72 Decibal
Physical
Maximum Height
1300 Mm
Maximum Width
500 Mm
Maximum Depth
850 Mm
Shipping Height
1500 Mm
Shipping Width
625 Mm
Shipping Depth
975 Mm
Net Weight
227 Kg
Shipping weight
257 Kg
Colour
RAL 9003
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 - 1476.3 Meters
Storage Temperature
-25 - 55 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
0 - 15000 Meters
Online thermal dissipation
27297 Btu/Hr
Protection Class
IP20
Compliances
Compliance
BIS
Approvals
EN/IEC 62040-1, IEC 62040-2, IEC 62040-3, IEC 62040-4
Other Environmental Compliance
Compliant
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes

Features

E3MUPS160KHS Features
Easy UPS 3M Features & Benefits
Convenience
Easy Loop Test
Verifies UPS performance before you connect your load, without the need for a load bank.
Easy to install fast
Quickly roll the compact and lightweight UPS into position.
Front-Access Servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high
Straightforward installation
Including the input, output, and bypass breakers, as well as the Emergency Power Off (EPO) switch, s
Protection
Replaceable dust filters
protect the UPS in harsh environments.
Wide Input Voltage Window
Saves your battery power for when you really need it - during power cuts!
Parallel capability
Multiple units can be placed in parallel to meet power capacity and redundancy requirements
Optional SNMP Card
When you purchase the SNMP card, you can monitor and manage UPS status remotely through the UPS Web

Documentation

Item Catalogue
APC Easy Model 160 KVA
pdf
APC - Easy UPS 3 Series 10-200 kVA Brochure
pdf

Options

Services

© Copyright 2005 | apcups.co.in. All right reserved.