Specification
Output Capacity (KVA )
120 Kva
Output Capacity (KW )
120 Kw
Output Power Factor
1 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
>0.99 %
Output Voltage Distortion
<3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Other Input Voltage
380 - 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
40 - 70 Hz
Input Voltage Range (Output Derated)
150 - 342 Volt
Input voltage range for main operations
342 - 477 Volt
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Current (Maximum)
207 Amp.
Battery Position Option
External
Battery Circuit Breaker
Optional
Approved Battery Capacity (AH)
120 - 400 Amp.
Battery DC Bus
432 - 600 Vdc
Battery Type Compatibility
Sealed Maintenance Free (SMF) / Valve Regulated Lead Acid (VRLA) type, Flooded / tubular / vented type
Communication & Management
Control panel
Touch Screen LCD User Interface
Power Management Software
In-Built
Interface Port(s)
E3M_ColdStart, E3M_parallel, E3S_TempSensor
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
72 Decibal
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 - 1476.3 Meters
Storage Temperature
-25 - 55 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
0 - 15000 Meters
Online thermal dissipation
20473 Btu/Hr
Approvals
EN/IEC 62040-1, IEC 62040-2, IEC 62040-3, IEC 62040-4
Other Environmental Compliance
Compliant
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449