APC - Schneider Electric Make 1 KVA 1:1 Phase On-Line UPS | apcups.co.in

Contact Us

Product UPS System On Line UPS APC - Schneider Electric Make 1 KVA 1:1 Phase On-Line UPS

APC - Schneider Electric Make 1 KVA 1:1 Phase On-Line UPS

UPS System On Line UPS

0.00

>90% efficiency (Double-conversion) • Save Rs 2k every year* • Save even more in Green mode – 93% efficiency High-Power Charger : Allows up to 1.15 hrs backup without added charger at full load Selectable charging current : 2A/4A/7.5A – Flexibility to use different capacity batteries for all kinds of runtime. SMF / Flooded Battery type selection High Ambient Temp compatibility Upto 50C at de-rated capacity* Graphical LCD easy-to-use interface & Audible Alarm with mute option SmartSlot for all management card options Genset-compatible Remote Management of UPS thru PCBE

Model SRC1KUXIX834

Reset default

Specification

Output Specification
Output Capacity (KVA )
1 KVA
Output Capacity (KW )
.8 KW
Output Power Factor
.8
Output Phase
1 Phase
Other Output Phase
Output Voltage
230 Volt
Other Output Voltage
220 Or 240 Volt
Efficiency at Full Load
> 90 %
Output Voltage Distortion
< 1 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Load Crest Factor
Output Voltage THD
< 3 %
Transfer Time
<0 Ms
Output Waveform type
Sine Wave
Output Connections
3 Pin Indian Socket (04 Nos.)
Bypass
In-Built
UPS Parallel Upto
Overload Capacity
Input Specification
Input Voltage
230 Volt
Other Input Voltage
220 Or 240 Volt
Input Phase
1 Phase
Other Input Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
110 - 285Volt
Input voltage range for main operations
140 - 280 Volt
Input frequency Range
40 - 70 Hz
Input Power Factor
> 0.98
Input Connections
3-Pin 6A Indian Socket
Input Protection
Thermal Circuit Breaker
Batteries & Runtime
Internal Battery Capacity (VAH)
VAH
Approved Battery Capacity (AH)
7 - 100 Amp.
Battery DC Bus
24 - VDC
Maximum Charger Capacity
7.5 Amp.
Battery Position Option
Battery Type Compatibility
SMF Battery
Batteries Recharge Time upto 90%
< 10 Hrs.
Communication & Management
Control panel
Multi-function LCD status and control console
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
DB-9 RS-232, Smart-Slot
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
<45 Decibal
Physical
Maximum Height
220 Mm
Maximum Width
145 Mm
Maximum Depth
397 Mm
Shipping Height
230 Mm
Shipping Width
472 Mm
Shipping Depth
325 Mm
Net Weight
4.1 Kg
Shipping weight
5.5 Kg
Rack Height(U)
Colour
Black
Environmental
Operating Temperature
0 - °C 40
Operating Relative Humidity
0 - % Rh 95
Operating Elevation
0 - 914 Meters
Storage Temperature
-20 - °C 60
Storage Relative Humidity
0 - 95 % Rh
Storage Elevation
0 - 4572 Meters
Compliances
Compliance
Approvals
Other Environmental Compliance
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes

Features

Smart UPS On Line Features & Benefits
Serviceability
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batter
Audible alarms
Provides notification of changing utility power and UPS power conditions
Disconnected battery notification
Warns when a battery is not available to provide backup power.
Predicitive failure notification
Provides early-warning fault analysis ensuring proactive component replacement.
Protection
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power disturbances.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Resettable circuit breaker
Easy recovery from overloads; no need to replace a fuse. (Not available on Wall Tap SKUs)
Cold-start Capable
Provides Temporary Battery Power When The Utility Power Is Out.
Safety-agency Approved
Ensures the product has been tested and approved to work safely with the connected service provider
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without us
Marketing Features
Save time with easy and convenient remote/network accessibility
Network manageable via serial, USB or Ethernet. Includes Powerchute® Software for convenient monitor
Low operating and maintenance costs with proven reliability and intelligent battery management
Intelligent battery management, pioneered by APC, maximizes battery performance and life through int
Avoids costly power problems by keeping your IT equipment and data protected and available
Network grade power conditioning protects from damaging surges and disruptive noise. The double conv
Peace of mind that comes with full equipment compatibility and reliability of a leader
Provides pure sine wave output which is recommended by server manufacturers using active power facto
Adoptbility
Rack/Tower convertible
Protects the initial investment in the UPS when migrating from tower to rack-mount environment.
Plug-and-Play external batteries
Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
Flash upgradeable firmware
Install maintenance releases of firmware remotely using FTP.
Manageability
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
SmartSlot
Customize UPS capabilities with management cards.
Network manageable
Provides remote power management of the UPS over the network.
Serial connectivity
Provides management of the UPS via a serial port.
LED status indicators
Quickly understand unit and power status with visual indicators.
Availabilty
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Automatic restart of loads after UPS shutdown
Automatically starts up the connected equipment upon the return of utility power.
Scalable runtime
Allows additional run time to be quickly added as needed.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
SRC1KUXI Features
General Features
APC Smart-UPS RC 1000VA 230V No Batteries India
High density, double-conversion on-line power protection with scalable runtime
Includes: Basic UPS signalling RS-232 cable, Installation guide, User Manual
Highlights
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Cold-start Capable
Provides Temporary Battery Power When The Utility Power Is Out.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without us

Documentation

Item Catalogue
SRC1KUXIX834
pdf
Item Manuals and Warranties
SRC1KUXIX834
pdf

Options

Services

© Copyright 2005 | apcups.co.in. All right reserved.