Specification
Output Capacity (KVA )
400 KVA
Output Capacity (KW )
400 KW
Output Power Factor
1 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 95 %
Output Voltage THD
< 3% linear load and <5% non-linear load
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Other Input Voltage
380 Or 415 Volt
Input Voltage Range (Output Derated)
323 - 477 Volt
Input voltage range for main operations
323 - 477 Volt
Input Short Circuit Current (Maximum)
35 kAmps.
Battery DC Bus
432 - 600 VDC
Battery Type Compatibility
SMF/ Li-Ion battery
Battery Position Option
External
Approved Battery Capacity (AH)
200 - 1000 Amp.
Battery Circuit Breaker
Optional
Communication & Management
Control panel
Touch Screen LCD User Interface
Power Management Software
In-Built
Interface Port(s)
DB-9 RS-232, Smart-Slot
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< 72 Decibal
Operating Temperature
0 - 30 °C
Operating Relative Humidity
0 - 95 %
Online thermal dissipation
79181 Btu/Hr
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449